The Yokogawa PS35*A, also cataloged as the Yokogawa PS35-A Power Supply Module, operates as a dedicated hardware component for delivering regulated DC power to I/O cards and nests within CENTUM VP, CENTUM XL, and u-XL network architectures.
| Parameter | Specification |
|---|---|
| Model | PS35*A (PS35-A) |
| Brand | Yokogawa |
| Origin | United States |
| Weight | 0.6 kg (Module baseline; alternative shipping packages list up to 1.2 kg) |
| Dimensions | Approx. 220 mm x 210 mm x 80 mm (Alternative package metrics: 45.7 cm x 5.1 cm x 17.8 cm) |
| Operating Temp | -10 to +55 deg C |
| Power Consumption | Power Capacity: ~85 W maximum |
| Input Voltage Range | 100-120 VAC or 200-240 VAC, 50/60 Hz |
| Output Voltage | 24 VDC regulated |
| Output Current | Up to 3.5 A |
| Isolation Boundaries | Galvanic isolation between input and output stages |
| Circuit Protection | Over-voltage, over-current, and short-circuit protection |
| Status Diagnostics | Integrated front-panel Power ON and Fault LEDs |
| Mounting Form Factors | Compatible with horizontal (RYH-32) and vertical (RYV-11) nests |
| Operating Humidity | 5% to 95% RH, non-condensing |
The Yokogawa PS35*A incorporates robust galvanic isolation barriers to decouple the AC incoming utility grid from the low-voltage DC logic backplane. The internal circuit architecture generates a steady 24 VDC output regulating up to 3.5 A, utilizing built-in over-voltage, over-current, and short-circuit trip thresholds to isolate downstream I/O hardware cards during localized component failures. Integrated front-panel LED indicators output continuous diagnostic signals, changing state immediately if an internal rail drop or overload fault disrupts the 85 W power allocation limit.
Q: What are the consequences of overloading the 3.5 A output current envelope?
A: Exceeding the 3.5 A capacity activates the internal over-current protection circuit, forcing the module to limit output voltage or shut down the 24 VDC rail completely. The front-panel Power ON LED will extinguish or toggle to a Fault indication state until the overload condition is physically cleared.
Q: Is manual voltage configuration required to switch between 100-120 VAC and 200-240 VAC input links?
A: Input voltage parameters match standard industrial power schedules. Depending on the specific terminal configuration of the host RYH-32 or RYV-11 nest assembly, the input wiring must be terminated at the designated low or high AC voltage terminals to ensure correct input transformation.
Q: Can this power module be hot-swapped within legacy nest configurations during live process operations?
A: No, unassisted hot-swapping is prohibited. Because this module serves as the primary 85 W supply rail for adjacent I/O cards inside the nest, removing the unit while energized cuts off power to all shared channels, dropping current loops and causing a total loop signal disruption.
Ships within 48 hours · Estimated delivery Jul 22 - Jul 27