The Woodward 5501-467, also cataloged as the 5501-467 Main Power Supply, operates as a dedicated hardware component for delivering regulated DC power within MicroNet Simplex platforms.
| Parameter | Specification |
|---|---|
| Model | 5501-467 |
| Brand | Woodward |
| Origin | USA |
| Weight | 2.32 kg (5.11 lbs) |
| Dimensions | 7.5 cm x 24.6 cm x 26.1 cm |
| Operating Temp | 0 to +60 deg C |
| Power Consumption | Power conversion limits up to 531 W (DC) / 1062 VA (AC) |
| 24 Vdc Input Range | 18 to 36 Vdc (20-32 Vdc nominal) |
| 120 Vac/dc Input Range | 88-132 Vac (47-63 Hz) / 100-150 Vdc |
| Max Input Current (24 Vdc) | 29.5 A |
| Max Input Current (120 Vac) | 12.1 A |
| Holdup Time | 5 ms @ 24 Vdc / 1 Cycle @ 120 Vac |
| Diagnostic Indicators | Input Fault, Power Supply Fault, Overtemperature, OK |
| Fuse/Breaker Requirements | 50 A Time Delay (24 V) / 20 A (120 V) |
The power module performs direct energy conversion to feed processing units and variable geometry actuators linked to the electronic governor network. The design integrates a specialized 1-cycle ride-through holdup circuit at 120 Vac to suppress momentary grid voltage drops, preventing unintended processor resets that disrupt actuator loop feedback response routines. To withstand localized electrical disturbances inherent to heavy industrial power grids, the module features built-in harmonic distortion suppression stages and heavy-duty industrial shielding. Internal heat sink dissipation profiles are calibrated to sustain maximum power outputs of 531 W under continuous operations within hot turbine cabinet enclosures.
Q: What are the discrete line isolation behaviors when running a dual-input configuration?
A: The internal switching architecture manages distinct voltage inputs separately. It accepts low-voltage 24 Vdc or high-voltage 120 Vac/Vdc standards, protecting the central MicroNet backplane components from line transients via internal galvanic boundaries.
Q: How does the power supply handle localized thermal overloads?
A: The device monitors its internal thermal thresholds via self-diagnostic circuitry. If internal limits are exceeded, the hardware trips the front-panel Overtemperature indicator LED and modulates or shuts down its output states to protect internal component groups.
Q: What are the exact protective fusing requirements for the distinct input lines?
A: For the 24 Vdc input loop, a 50 A time-delay fuse or circuit breaker is required. For the 120 V input circuit, the line must be protected by a 20 A rated branch circuit breaker or fuse.